Rockwell Automation 284 ArmorStart User Manual User Manual
Page 107

Bulletin 283 Programmable Parameters
4-17
➊
Not available on the Bulletin 283A.
On-to-Off Delay
This parameter allows the
installer to program a time
duration before an input is
reported “OFF”
Parameter Number
31
➊
Access Rule
GET/SET
Data Type
UINT
Group
User I/O
Units
ms
Minimum Value
0
Maximum Value
65.000
Default Value
0
In Sink/Source
This parameter allows the
installer to program the inputs to
be sink or source.
0=Sink
1=Source
Parameter Number
32
➊
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA Pr FltState
This parameter in conjunction
with Parameter 34 defines how
Output A will respond when a
protection trip occurs. When set
to “1”, Output A continues to
operate as command via the
network. When set to “0”, Output
A will open or close as
determined by setting in
Parameter 34
Parameter Number
33
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA Pr FltValue
This parameter determines the
state the Out A assumes when a
trip occurs and Parameter 33 is
set to “0”
0 = Open
1 = Close
Parameter Number
34
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0