Rockwell Automation 284 ArmorStart User Manual User Manual
Page 417
![background image](/manuals/577766/417/background.png)
Bulletin 284 CIP Information
D-17
Instances 8…11 are ZIP Consumers. The following instance
attributes will be supported:
Table D.38 Connection Object instance 8...11 Attributes
The following services are implemented for the Connection Object
Table D.39 Connection Objects Common Services:
Attribute
ID
Access
Rule
Name
Data
Type
Value
1
Get
State
USINT
0=nonexistant
1=configuring
3=established
2
Get
Instance Type
USINT
1=I/O Connection
3
Get
Transport Class Trigger
USINT
0x20 (COS,
unacknowledged)
4
Get
Produced Connection ID
UINT
FFFF (not producing data)
5
Get
Consumed Connection ID
UINT
01101xxxxxx
xxxxxx=node address
6
Get
Initial Comm Characteristics
USINT
0xF0 (unacknowledged)
7
Get
Produced Connection Size
UINT
0
8
Get
Consumed Connection Size
UINT
8
9
Get/Set
Expected Packet Rate
UINT
in milliseconds
12
Get
Watchdog Action
USINT
2=auto reset
13
Get
Produced Connection Path
Length
UINT
0
14
Get
Produced Connection Path
0
15
Get
Consumed Connection Path
Length
UINT
8
16
Get
Consumed Connection Path
21 0E 03 25 01 00 30 02
Service
Code
Implemented for
Service
Name
Class
Instance
0x05
No
Yes
Reset
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single