Bulletin 284 Programmable Parameters for Volts per Hertz Controllers

Reverse Disable

Enables/disables the function that allows the direction of the motor rotation to be
changed. The reverse command may come from a digital command or serial
command. All reverse inputs including two-wire Run Reverse will be ignored with
reverse disabled.
0 = Disabled
1 = Enabled

Parameter Number

195

Related Parameters

106

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Flying Start En
Sets the condition that allows the drive to reconnect to a spinning motor at actual
RPM.
0 = Disabled
1 = Enabled

Parameter Number

196

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Compensation
Enables/disables correction options that may improve problems with motor
instability
0 = Disabled
1 = Electrical (Default)
Some drive/motor combinations have inherent instabilities which are exhibited as
non-sinusoidal motor currents. This setting attempts to correct this condition
2 = Mechanical
Some motor/load combinations have mechanical resonances which can be excited
by the drive current regulator. This setting slows down the current regulator
response and attempts to correct this condition.
3 = Both

Parameter Number

197

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

3

Default Value

1

SW Current Trip
Enables/disables a software instantaneous (within 100 ms) current trip.

Parameter Number

198

Related Parameters

133

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 A

Minimum Value

0.0

Maximum Value

Drive rated amps x 2

Default Value

0.0 (Disabled)

Process Factor
Scales the output frequency value displayed by Parameter 110 (Process Display).
Output Freq x Process Factor = Process Display

Parameter Number

199

Related Parameters

110

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1

Minimum Value

0.1

Maximum Value

999.9

Default Value

30.0

Stop drive before changing this parameter.