Bulletin 283, continued, A-6 specifications – Rockwell Automation 284 ArmorStart User Manual User Manual
Page 326
![background image](/manuals/577766/326/background.png)
A-6
Specifications
Bulletin 283, Continued
Electrical Ratings
UL/NEMA
IEC
Environmental
Operating Temperature Range
–20…40°C (–4…104°F)
Storage and Transportation
temperature range
–25….85°C (–13…185°F)
Altitude
2000 m
Humidity
5…95% (non-condensing)
Pollution Degree
3
Mechanical Resistance to Shock
Operational 15
G
Non-Operational 30
G
Resistance to Vibration
Operational
1 G, 0.15 mm (0.006 in.) displacement
Non-Operational 2.5
G,
0.38 mm (0.015 in.) displacement
Control Power and Safety Monitor
Terminal Cable Size
Primary/ Secondary Terminal:
#18…#10 AWG
Primary/ Secondary Terminal:
1.0 …4.0 mm
2
Tightening Torque
6.2 in·lb
0.7 N·m
Line Power Terminal cable size
#16…#10 AWG
1.5…4.0 mm
2
Tightening Torque
4.5 in·lb
0.5 N·m
Ground Terminal cable size
#18…#10 AWG
1.0…4.0 mm
2
Tightening Torque
4.5 in·lb
0.5 N·m
Enclosure Ratings
NEMA Type 4/12/13 or NEMA Type 4X
IP67 or IP69K
Approximate Shipping Weight
16.8 kg (37 lbs.)
Other Rating
EMC Emission levels
Conducted Radio Frequency Emissions
Class A
Radiated Emissions
Class A
EMC immunity levels
Electrostatic Discharge
4 kV contact and 8 kV Air
Radio Frequency Electromagnetic Field
10 V/m
Fast Transient
2 kV
Surge Transient
1 kV L-L, 2 kV L-N (Earth)
Overload Characteristics
Overload Current Range
1.1…3.0 A
3.0…5.5 A
5.3…7.6 A
6.3…16 A
Trip Class
10
Trip Rating
120% of FLC setting
Number of poles
3
DeviceNet Specifications
DeviceNet Supply Voltage Rating
Range 11…25V DC, 24V DC Nominal
DeviceNet Input Current
167 mA @ 24V DC - 4.0 W
364 mA @ 11V DC - 4.0 W
External Devices powered by DeviceNet
Sensors Inputs 4 * 50 mA - total 200 mA
Total w/max. Sensor Inputs (4)
367 mA @ 24V DC - 8.8 W
DeviceNet Input Current Surge
15 A for 250 µs
DeviceNet Communications
Baud Rates
125, 250, 500 kbps
Distance Maximum
500 m (1630 ft) @ 125 kbps
200 m (656 ft) @ 250 kbps
100 m (328 ft) @ 500 kbps
Certifications
cULus (File No. E96956)
UL 508
EN/IEC 60947-4-2
CE Marked per Low Voltage Directive 73/23/EEC and EMC Directive 89/336/EEC