Step logic parameters – Rockwell Automation 284 ArmorStart User Manual User Manual
Page 477
Step Logic, Basic Logic and Timer/Counter Functions
J-5
Step Logic Parameters
Digit 3
Digit 2
Digit 1
Digit 0
0
0
F
1
Setting
Accel/Decel Parameters Used
Step Logic Output State
Commanded Direction
0
1
Off
FWD
1
1
Off
REV
2
1
Off
No Output
3
1
On
FWD
4
1
On
REV
5
1
On
No Output
6
2
Off
FWD
7
2
Off
REV
8
2
Off
No Output
9
2
On
FWD
A
2
On
REV
b
2
On
No Output
Setting
Logic
0
Jump to Step 0
1
Jump to Step 1
2
Jump to Step 2
3
Jump to Step 3
4
Jump to Step 4
5
Jump to Step 5
6
Jump to Step 6
7
Jump to Step 7
8
End Program (Normal Stop)
9
End Program (Coast to Stop)
A
End Program and Fault (F2)
Setting
Description
Logic
0
Skip Step (jump immediately).
SKIP
1
Step based on the time programmed in the respective (Stp Logic Time x) parameter.
TIMED
2
Step if Logic In1 is active (logically true).
TRUE
3
Step if Logic In2 is active (logically true).
TRUE
4
Step if Logic In1 is not active (logically false).
FALSE
5
Step if Logic In2 is not active (logically false).
FALSE
6
Step if either Logic In1 or Logic In2 is active (logically true).
OR
7
Step if both Logic In1 and Logic In2 is active (logically true).
AND
8
Step if neither Logic In1 or Logic In2 is active (logically true).
NOR