User i/o group – Rockwell Automation 284 ArmorStart User Manual User Manual
Page 189

Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
6-15
User I/O Group
➊Not available with the Bulletin 284A.
Off-to-On Delay
➊
This parameter allows the installer to program a time duration before being reported
ON.
Parameter Number
30
Access Rule
GET/SET
Data Type
UINT
Group
User I/O
Units
ms
Minimum Value
0
Maximum Value
65.000
Default Value
0
On-to-Off Delay
➊
This parameter allows the installer to program a time duration before being reported
OFF.
Parameter Number
31
Access Rule
GET/SET
Data Type
UINT
Group
User I/O
Units
ms
Minimum Value
0
Maximum Value
65.000
Default Value
0
In Sink/Source
➊
This parameter allows the installer to program the inputs to be sink or source.
0 = Sink
1 = Source
Parameter Number
32
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA Pr FltState
This parameter in conjunction with Parameter 34 defines how Output A will respond
when a trip. When set to 1, Output A continue to operate as command via the
network. When set to 0, Output A will open or close as determined by setting in
Parameter 34.
Parameter Number
33
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA Pr FltValue
This parameter determines the state the Out A assumes when a trip occurs and
Parameter 33 is set to 0.
0 = Open
1 = Close
Parameter Number
34
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0