Overload object — class code 0x002c – Rockwell Automation 284 ArmorStart User Manual User Manual
Page 371
Bulletin 280/281 CIP Information
B-27
Overload Object — CLASS CODE
0x002c
No class attributes are supported for the Overload Object.
A single instance (instance 1) of the Overload Object is supported for
Bulletin 280/281:
Table B.54 Overload Object Instance Attributes
The following common services are implemented for the Overload
Object:
Table B.55 Acknowledge Handler Object Common Services
Attribute ID
Access Rule
Name
Data Type
Value
3
Get/Set
FLA Setting
BOOL
xxx.x Amps
4
Get/Set
Trip Class
USINT
1=10
2=15
3=20
5
Get
Average Current
UINT
xxx.x Amps
7
Get
% Thermal Utilized
USINT
xxx% FLA
8
Get
Current L1
UINT
xxx.x Amps
9
Get
Current L2
UINT
xxx.x Amps
10
Get
Current L3
UINT
xxx.x Amps
190
Get/Set
FLA Setting Times 10
BOOL
xxx.x Amps
192
Get
Avg. Current Times 10
UINT
xxx.x Amps
193
Get
Current L1 Times 10
UINT
xxx.x Amps
194
Get
Current L2 Times 10
UINT
195
Get
Current L3 Times 10
UINT
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single