Wiring – Rockwell Automation 284 ArmorStart User Manual User Manual
Page 48
2-24
Installation and Wiring
Wiring
Power, Control, Safety Monitor Inputs, and Ground Wiring
Table 2.1 provides the power, control, and ground wire capacity and
the tightening torque requirements. The power, control, ground, and
safety monitor terminals will accept a maximum of two wires per
terminal.
Table 2.1
Power, Control, Safety Monitor Inputs, Ground Wire Size, and
Torque Specifications
Terminals
Wire Size
Torque
Wire Strip Length
Power
and
Ground
Primary/Secondary
Terminal:
1.5…4.0 mm
2
(#16 …#10 AWG)
Primary Terminal:
10.8 lb.-in.
(1.2 N•m)
Secondary Terminal:
4.5 lb.-in
(0.5 N•m)
0.35 in. (9 mm)
Control and Safety
Monitor Inputs
1.0 mm
2
…4.0 mm
2
(#18…#10 AWG)
6.2 lb.-in
(0.7 N•m)
0.35 in. (9 mm)