Rockwell Automation 284 ArmorStart User Manual User Manual
Page 120

4-30
Bulletin 283 Programmable Parameters
Table 4.2
FLA Setting Ranges and Default Values (with indicated setting
precision)
➊
Recommended maximum start time is 15 seconds.
➋
Recommended maximum current limit setting is 350%.
FLA Current Range (A)
Default Value
Minimum Value
Maximum Value
1.1
3.0
1.1
3.0
5.5
3.0
5.3
7.6
5.3
6.3
16.0
6.3
OL Reset Level
This parameter allows the
installer select the % Thermal
Capacity which an overload can
be cleared
Parameter Number
108
Access Rule
GET/SET
Data Type
USINT
Group
Soft Start Setup
Units
% FLA
Minimum Value
0
Maximum Value
100
Default Value
75
Start Time ➊
This parameter allows the
installer to select the start time of
1…45 seconds
Parameter Number
109
Access Rule
GET/SET
Data Type
USINT
Group
Soft Start Setup
Units
Sec
Minimum Value
1
Maximum Value
45
Default Value
10
Start Mode
This parameter allows the
installer to select either soft stop
or current limit
1= Current Limit
0= Soft Start
Parameter Number
110
Access Rule
GET/SET
Data Type
BOOL
Group
Soft Start Setup
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Current Limit ➋
This parameter allows the
installer to select the value of the
current limit setting of
150…600% of the full load amps
Parameter Number
111
Access Rule
GET/SET
Data Type
UINT
Group
Soft Start Setup
Units
% of Motor FLA
Minimum Value
150
Maximum Value
600
Default Value
350