beautypg.com

Rockwell Automation 284 ArmorStart User Manual User Manual

Page 191

background image

Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

6-17

OutB Pr FltValue
This parameter determines the state the Out B assumes when a trip occurs and
Parameter 39 is set to 0.
0 = Open
1 = Close

Parameter Number

40

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutB DN FltState
This parameter in conjunction with Parameter 42 defines how Output B will respond
when a DeviceNet network fault occurs. When set to 1, Output B will hold state prior
to trip occurrence. When set to 0, Output B will open or close as determined by
setting in Parameter 42.

Parameter Number

41

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutB DN FltValue
This parameter determines the state that Output B assumes when a DeviceNet
network fault occurs and Parameter 41 is set to 0.
0 = Open
1 = Close

Parameter Number

42

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutB DN IdlState
This parameter in conjunction with Parameter 44 defines how Output B will respond
when the DeviceNet network is idle. When set to 0, Output B will open or close as
determined by the setting in Parameter 44.
The DN Flt parameters supersede the Dn Idl parameters.

Parameter Number

43

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutB DN IdlValue
This parameter determines the state that Output B assumes when the network is
idle and Parameter 43 is set to 0.
0 = Open
1 = Close

Parameter Number

44

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O

Units

Minimum Value

0

Maximum Value

1

Default Value

0

This manual is related to the following products: