Rockwell Automation 284 ArmorStart User Manual User Manual
Page 139

Bulletin 284 Programmable Parameters for Volts per Hertz Controllers
5-17
➊ Not available on Bulletin 284A units. .
In Sink/Source
This parameter allows the installer to program the inputs to be sink or source.
0 = Sink
1 = Source
Parameter Number
32 ➊
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA Pr FltState
This parameter in conjunction with Parameter 34 defines how Output A will respond
when a trip. When set to 1, Output A continue to operate as command via the
network. When set to 0, Output A will open or close as determined by setting in
Parameter 34.
Parameter Number
33
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA Pr FltValue
This parameter determines the state the Out A assumes when a trip occurs and
Parameter 33 is set to 0.
0 = Open
1 = Close
Parameter Number
34
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA DN FltState
This parameter in conjunction with Parameter 36 defines how Output A will respond
when a DeviceNet network fault occurs. When set to 1, Output A will hold state prior
to trip occurrence. When set to 0, Output A will open or close as determined by
setting in Parameter 36.
Parameter Number
35
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA DN FltValue
This parameter determines the state that Output A assumes when a DeviceNet
network fault occurs and Parameter 35 is set to 0.
0 = Open
1 = Close
Parameter Number
36
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0