Devicenet group – Rockwell Automation 284 ArmorStart User Manual User Manual
Page 182

6-8
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
DeviceNet Group
Network Override
This parameter allows for the local logic to override a Network fault.
0 = Disable
1 = Enable
Parameter Number
8
Access Rule
GET/SET
Data Type
BOOL
Group
DeviceLogix
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Comm Override
This parameter allows for local logic to override a loss of an I/O connection.
0 = Disable
1 = Enable
Parameter Number
9
Access Rule
GET/SET
Data Type
BOOL
Group
DeviceLogix
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Autobaud Enable
When this parameter is enabled, the device will attempt to determine the network
baud rate and set its baud rate to the same, provided network traffic exists. At least
one node with an established baud rate must exist on the network for autobaud to
occur.
0 = Disable
1 = Enable
Parameter Number
10
Access Rule
GET/SET
Data Type
BOOL
Group
DeviceNet
Units
—
Minimum Value
0
Maximum Value
1
Default Value
1
Consumed I/O Assy
This parameter selects the format of the I/O data consumed
Parameter Number
11
Access Rule
GET/SET
Data Type
USINT
Group
DeviceNet
Units
—
Minimum Value
0
Maximum Value
188
Default Value
164
Produced I/O Assy
This parameter selects the format of the I/O data produced.
Parameter Number
12
Access Rule
GET/SET
Data Type
USINT
Group
DeviceNet
Units
—
Minimum Value
0
Maximum Value
190
Default Value
165