Rockwell Automation 284 ArmorStart User Manual User Manual
Page 159

Bulletin 284 Programmable Parameters for Volts per Hertz Controllers
5-37
Accel Time 1
Sets the rate of acceleration for all speed increases.
Parameter Number
139
Related Parameters
138, 140, 151, 152, 167,
170…173
Access Rule
GET/SET
Data Type
UINT
Group
Basic Program Setup
Units
0.1 sec
Minimum Value
0.0 sec
Maximum Value
600.0 sec
Default Value
10.0 sec
Decel Time 1
Sets the rate of deceleration for all speed decreases.
Parameter Number
140
Related Parameters
138, 139, 151, 152, 168,
170…173
Access Rule
GET/SET
Data Type
UINT
Group
Basic Program Setup
Units
0.1 sec
Minimum Value
0.1 sec
Maximum Value
600.0 sec
Default Value
10.0 sec
Reset To Defaults
Resets all parameter values to factory defaults.
0 = Ready/Idle (Default)
1 = Factory Rset
Parameter Number
141
Access Rule
GET/SET
Data Type
BOOL
Group
Basic Program Group
Units
—
Minimum Value
1
Maximum Value
1
Default Value
0
Maximum Freq
Accel Time
--------------------------------------
Accel Rate
=
Maximum Freq
Decel Time
--------------------------------------
Decel Rate
=
Stop drive before changing this parameter.
Motor OL Ret
Enables/disables the Motor overload Retention function. When Enabled, the value
held in the motor overload counter is saved at power-down and restored at power-
up. A change to this parameter setting resets the counter.
0 = Disabled (Default)
1 = Enabled
Parameter Number
143
Access Rule
GET/SET
Data Type
BOOL
Group
Basic Program Group
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0