Bulletin 284 Programmable Parameters for Volts per Hertz Controllers
5-23
Drvin DNFltState
This parameter, in conjunction with Parameter 52, defines how the Drive Digital
Inputs 1…2 will respond when a DeviceNet fault occurs. When set to 1, Drive
Digital Inputs 1…2 hold last state occurs. When set to 0, will go to DnFlt Value on
DN faults as determined by Parameter 52.
0 = Go to Fault Value
1 = Hold Last State
Parameter Number
51
Access Rule
GET/SET
Data Type
BOOL
Group
Drive DeviceNet
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Drvin DNFlt Value
This parameter determines if the drive will be commanded in the event of a
DeviceNet fault.
0 = OFF
1 = ON
Parameter Number
52
Access Rule
GET/SET
Data Type
BOOL
Group
Drive DeviceNet
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Drvin DNIdlState
This parameter, in conjunction with Parameter 54, defines how the Drive Digital
Input 1…2 will respond when a DeviceNet network is idle. When set to 1, hold to
last state occurs. When set to 0, will go to DnFlt Value on DN faults as determined
by Parameter 54.
0 = Go to Fault Value
1 = Hold Last State
Parameter Number
53
Access Rule
GET/SET
Data Type
BOOL
Group
Drive DeviceNet
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
StrtrDN IdlValue
This parameter determines the state that Digital Inputs 1…2 assume when the
network is idle and Parameter 53 is set to 0.
0 = OFF
1 = ON
Parameter Number
54
Access Rule
GET/SET
Data Type
BOOL
Group
Drive DeviceNet
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0