Advanced program group – Rockwell Automation 284 ArmorStart User Manual User Manual
Page 160
5-38
Bulletin 284 Programmable Parameters for Volts per Hertz Controllers
Advanced Program Group
151 (Digital In 1 SEL)
152 (Digital In 2 SEL)
Selects the function for the digital inputs.
See Table 5.B for details
Parameter Number
151, 152
Related Parameters
112, 114, 138…140, 167,
168, 170…173, 178, 179
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
—
Minimum Value
0
Maximum Value
26
Default Value
4
Table 5.B Digital Inputs Options
Options
Description
0
Not Used
Terminal has no function but can be read over network communication via Parameter 114 (Dig In Status).
1
Acc & Dec2
•
When active, Parameter 167 (Accel Time 2) and Parameter 168 (Decel Time 2) are used for all ramp rates
except Jog.
•
Can only be tied to one input.
2
Jog
•
When input is present, drive accelerates according to the value set in Parameter 179 (Jog Accel/Decel) and
ramps to the value set in Parameter 178 (Jog Frequency).
•
When the input is removed, drive ramps to a stop according to the value set in Parameter 179 (Jog Accel/
Decel).
•
A valid Start command will override this input.
3
Aux Fault
When enable, an F2 Auxiliary Input fault will occur when the input is removed.
4
Preset Freq
(Parameters 151
and 152 Default)
Refer to Parameters 170…173 and 174…177.
5…25
Not Used
Reserved
26
Anlg Invert
Option not valid for Bulletin 284 ArmorStart Distributed Motor Controller
Stop drive before changing this parameter.