Rockwell Automation 284 ArmorStart User Manual User Manual
Page 218
6-44
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Figure 6.4 Overload Trip Curves
Figure 6.5
Motor OL Select
Drive provides Class 10 motor overload protection. Setting 0…2 select the derating
factor for I
2
t overload function.
0 = No Derate
1 = Min. Derate
2 = Max. Derate
Parameter Number
190
Related Parameters
132, 133
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
1
Minimum Value
0
Maximum Value
2
Default Value
0
% of P132 (Motor NP Hertz)
% of P132 (Motor NP Hertz)
% of P132 (Motor NP Hertz)
% of P133 (Motor OL Current)
% of P133 (Motor OL Current)
% of P133 (Motor OL Current)
PWM Frequency
Sets the carrier frequency the PWM output waveform. The Figure 6.5 provides
derating guidelines based on the PWM frequency setting.
Parameter Number
191
Related Parameters
224
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.l Hz
Minimum Value
2.0 Hz
Maximum Value
16.0 Hz
Default Value
4.0 Hz