Rockwell Automation 284 ArmorStart User Manual User Manual
Page 172

5-50
Bulletin 284 Programmable Parameters for Volts per Hertz Controllers
Comm Loss Time
Sets the time that the drive remain in communication loss before implanting the
option selected in Parameter 205 (Comm Loss Action).
Parameter Number
206
Related Parameters
115, 205
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 sec
Minimum Value
0.1 sec
Maximum Value
60.0 sec
Default Value
15.0 sec
Comm Format
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.
Parameter Number
207
Anlg In 0…10V Lo
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.
Parameter Number
210
Anlg In 0…10V HI
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.
Parameter Number
211
Anlg In4…20MA LO
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.
Parameter Number
212
Anlg In4…20 mA HI
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.
Parameter Number
213
Slip Hertz @ FLA
Compensates for the inherent slip in an induction motor. This frequency is added to
the commanded output frequency based on motor current.
Parameter Number
214
Related Parameter
133
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 Hz
Minimum Value
0.0 Hz
Maximum Value
10.0 Hz
Default Value
2.0 Hz
Process Time Lo
Scales the time value when the drive is running at Parameter 134 (Minimum Freq).
When set to a value other than zero, Parameter 110 (Process Display) indicates the
duration of the process.
Parameter Number
215
Related Parameters
110, 134
Access Rule
GET/SET
Data Type
UNIT
Group
Advanced Setup
Units
Hz
Minimum Value
0.00
Maximum Value
99.99
Default Value
0.00