Rockwell Automation 284 ArmorStart User Manual User Manual
Page 141

Bulletin 284 Programmable Parameters for Volts per Hertz Controllers
5-19
OutB DN FltValue
This parameter determines the state that Output B assumes when a DeviceNet
network fault occurs and Parameter 41 is set to 0.
0 = Open
1 = Close
Parameter Number
42
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutB DN IdlState
This parameter in conjunction with Parameter 44 defines how Output B will respond
when the DeviceNet network is idle. When set to 0, Output B will open or close as
determined by the setting in Parameter 44.
The DN Flt parameters supersede the Dn Idl parameters.
Parameter Number
43
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutB DN IdlValue
This parameter determines the state that Output B assumes when the network is
idle and Parameter 43 is set to 0.
0 = Open
1 = Close
Parameter Number
44
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0