Rockwell Automation 284 ArmorStart User Manual User Manual
Page 140

5-18
Bulletin 284 Programmable Parameters for Volts per Hertz Controllers
OutA DN IdlState
This parameter in conjunction with Parameter 38 defines how Output A will respond
when the DeviceNet network is idle. When set to 0, Output A will open or close as
determined by the setting in Parameter 38.
The DN Flt parameters supersede the Dn Idl parameters.
Parameter Number
37
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA DN IdlValue
This parameter determines the state that Output A assumes when the network is idle
and Parameter 37 is set to 0.
0 = Open
1 = Closed
Parameter Number
38
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutB Pr FltState
This parameter in conjunction with Parameter 40 defines how Output B will respond
when a trip. When set to 1, Output B continue to operate as command via the
network. When set to 0, Output B will open or close as determined by setting in
Parameter 40.
Parameter Number
39
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutB Pr FltValue
This parameter determines the state the Out B assumes when a trip occurs and
Parameter 39 is set to 0.
0 = Open
1 = Close
Parameter Number
40
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutB DN FltState
This parameter in conjunction with Parameter 42 defines how Output B will respond
when a DeviceNet network fault occurs. When set to 1, Output B will hold state prior
to trip occurrence. When set to 0, Output B will open or close as determined by
setting in Parameter 42.
Parameter Number
41
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0