Bulletin 284 Programmable Parameters for Volts per Hertz Controllers
5-27
Zone #1 Offset
The byte offset into the ZIP data portion of the DeviceLogix data table to place the
chosen consumed data bytes for zone 1.
Parameter Number
82
Access Rule
GET/SET
Data Type
UINT
Group
ZIP Parameters
Units
—
Minimum Value
0
Maximum Value
7
Default Value
0
Zone #2 Offset
The byte offset into the ZIP data portion of the DeviceLogix data table to place the
chosen consumed data bytes for zone 2.
Parameter Number
83
Access Rule
GET/SET
Data Type
UNIT
Group
ZIP Parameters
Units
—
Minimum Value
0
Maximum Value
7
Default Value
0
Zone #3 Offset
The byte offset into the ZIP data portion of the DeviceLogix data table to place the
chosen consumed data bytes for zone 3.
Parameter Number
84
Access Rule
GET/SET
Data Type
UNIT
Group
ZIP Parameters
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Zone #4 Offset
The byte offset into the ZIP data portion of the DeviceLogix data table to place the
chosen consumed data bytes for zone 4.
Parameter Number
85
Access Rule
GET/SET
Data Type
UNIT
Group
ZIP Parameters
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Zone #1 EPR
The Expected Packet Rate in msec. for the zone 1 consuming connection. If
consumed data is not received in 4 times this value, the zone connection will time
out and “Zone #1 Health” will report 1 = Not Healthy.
Parameter Number
86
Access Rule
GET/SET
Data Type
UINT
Group
ZIP Parameters
Units
msec
Minimum Value
0
Maximum Value
65535
Default Value
75