Rockwell Automation 284 ArmorStart User Manual User Manual
Page 404
D-4
Bulletin 284 CIP Information
DeviceNet Object — CLASS CODE 0x0003
The following class attributes are supported for the DeviceNet Object:
Table D.6
DeviceNet Object Class Attributes
A single instance (Instance 1) of the DeviceNet Object will be
supported. The following instance attributes are supported:
Table D.7
DeviceNet Object Instance Attributes
➊
1M baud is only available on the Bulletin 284A.
➋
See Table D.8
Table D.8
Allocation_byte
The following services are implemented for the DeviceNet Object:
Table D.9
DeviceNet Object Common Services
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
2
Attribute
ID
Access
Rule
Name
Data Type
Value
1
Get/Set
Node Address
USINT
0…63
2
Get/Set
Baud Rate
USINT
0 = 125K
1 = 250K
2 = 500K
3 = 1M ➊
5
Get
Allocation Info
• Allocation Choice
• Master Node Addr
Structure of:
• BYTE
• USINT
Allocation_byte ➋
0…63 = address
255 = unallocated
8
Get
MAC ID Switch Value
BOOL
0…63
Bit 0
Explicit messaging
Bit 1
Polled I/O
Bit 4
COS I/O
Bit 5
Cyclic I/O
Bit 6
Acknowledge Suppression
Service
Code
Implemented for
Service
Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
0x4B
No
Yes
Allocate_Master/Slave _Connection_Set
0x4C
No
Yes
Release_Master/Slave _Connection_Set