Rockwell Automation 284 ArmorStart User Manual User Manual
Page 414
![background image](/manuals/577766/414/background.png)
D-14
Bulletin 284 CIP Information
Instance 2 is the Predefined Group 2 Connection Set Polled I/O
Message Connection. The following Instance 2 attributes are
supported
Table D.35 Connection Object Instance 2 Attributes:
Attribute
ID
Access
Name
Data
Type
Value
1
Get
State
USINT
0 = non-existent
1 = configuring
3 = established
4 = timed out
2
Get
Instance Type
USINT
1 = I/O Connection
3
Get
Transport Class Trigger
USINT
0x82 — Server,
Transport Class 2 (If
alloc_choice != polled
and ack suppression is
enabled then value =
0x80)
4
Get
Produced Connection ID
UINT
01111xxxxxx
xxxxxx = node address
5
Get
Consumed Connection ID
UINT
10xxxxxx101
xxxxxx = node address
6
Get
Initial Comm Characteristics
USINT
0x21
7
Get
Produced Connection Size
UINT
0…8
8
Get
Consumed Connection Size
UINT
0…8
9
Get/Set
Expected Packet Rate
UINT
in milliseconds
12
Get/Set
Watchdog Action
USINT
0 = transition to timed
out
1 = auto delete
2 = auto reset
13
Get
Produced Connection Path
Length
UINT
8
14
Get/Set
Produced Connection Path
21 04 00 25 (assy inst)
00 30 03
15
Get
Consumed Connection Path
Length
UINT
8
16
Get/Set
Consumed Connection Path
21 04 00 25 (assy inst)
00 30 03