Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
6-55
IR Voltage Drop
Value of volts dropped across the resistance of the motor stator.
Parameter Number
228
Related Parameters
227
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1V AC
Minimum Value
0.0
Maximum Value
230
Default Value
Based on Drive Rating
Flux Current Ref
Value of amps for full motor flux.
Parameter Number
229
Related Parameter
227
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.01 A
Minimum Value
0.00
Maximum Value
Motor NP Volts
Default Value
Based on Drive Rating
PID Trim Hi
Sets the maximum positive value that is added to a PID reference when PID trim is
used.
Parameter Number
230
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1
Minimum Value
0.0
Maximum Value
400.0
Default Value
60.0
PID Trim Lo
Sets the minimum positive value that is added to a PID reference when PID trim is
used.
Parameter Number
231
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1
Minimum Value
0.0
Maximum Value
400.0
Default Value
0.1
PID Ref Select
Enables/disables PID mode and selects the source of the PID reference. Valid PID
Ref Select for the Bulletin 284 ArmorStart are the following:
0 = PID Disable
1 = PID Setpoint
4 = Comm Port
5 = Setpnt Trim
8 = Comm, Trim
Parameter Number
232
Related Parameters
138, 222
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
—
Minimum Value
0
Maximum Value
9
Default Value
0
Stop drive before changing this parameter.