Rockwell Automation 284 ArmorStart User Manual User Manual
Page 108

4-18
Bulletin 283 Programmable Parameters
OutA DN FltState
This parameter in conjunction
with Parameter 36 defines how
Output A will respond when a
DeviceNet network fault occurs.
When set to “1”, Output A will
hold state prior to trip
occurrence. When set to “0”,
Output A will open or close as
determined by setting in
Parameter 36
Parameter Number
35
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA DN FltValue
This parameter determines the
state that Output A assumes
when a DeviceNet network fault
occurs and Parameter 35 is set to
“0”
0 = Open
1 = Close
Parameter Number
36
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA DN IdlState
This parameter in conjunction
with Parameter 38 defines how
Output A will respond when the
DeviceNet network is idle. When
set to “0”, Output A will open or
close as determined by the
setting in Parameter 38 The
DN Flt parameters supersede the
Dn Idl parameters
Parameter Number
37
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutA DN IdlValue
This parameter determines the
state that Output A assumes
when the network is idle and
Parameter 37 is set to “0”
0 = Open
1 = Close
Parameter Number
38
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutB Pr FltState
This parameter in conjunction
with Parameter 40 defines how
Output B will respond when a
protection trip occurs. When set
to “1”, Output B continue to
operate as command via the
network. When set to “0”, Output
B will open or close as
determined by setting in
Parameter 40
Parameter Number
39
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0