Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Figure 6.3
Start Boost
Sets the boost voltage (% of Parameter 131 [Motor NP Volts]) and redefines the Volts
per Hz curve when Parameter 184 (Boost Select) = 0 Custom V/Hz and Parameter
225 (Torque Perf Mode) = 0V/Hz.
Parameter Number
185
Related Parameters
131, 132, 134, 135, 184, 186,
187, 188, 225
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
1.1%
Minimum Value
0.0%
Maximum Value
25.0%
Default Value
2.5%
Parameter 131 (Motor NP Volts)
Parameter 188 (Maximum Voltage)
Parameter 134 (Minimum Freq)
Parameter 187 (Break Frequency)
Parameter 132 (Motor NP Hertz)
Parameter 135 (Maximum Freq)
Frequency
Voltage
Parameter 186 (Break V
oltage)
Parameter 186
(Start Boost)