Rockwell Automation 284 ArmorStart User Manual User Manual
Page 167

Bulletin 284 Programmable Parameters for Volts per Hertz Controllers
5-45
Figure 5.3 Overload Trip Curves
Maximum Voltage
Sets the highest voltage the drive will output.
Parameter Number
188
Related Parameters
104
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
1V AC
Minimum Value
20V AC
Maximum Value
Drive Rated Volts
Default Value
Drive Rated Volts
Current Limit
Maximum output current allowed before current limiting occurs
Parameter Number
189
Related Parameters
133
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 A
Minimum Value
0.1 A
Maximum Value
Drive rated amps X 1.8
Default Value
Drive rated amps X 1.5
Motor OL Select
Drive provides Class 10 motor overload protection. Setting 0…2 select the derating
factor for I
2
t overload function.
0 = No Derate
1 = Min. Derate
2 = Max. Derate
Parameter Number
190
Related Parameters
132
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
1
Minimum Value
0
Maximum Value
2
Default Value
0
% of P132 (Motor NP Hertz)
% of P132 (Motor NP Hertz)
% of P132 (Motor NP Hertz)
% of P133 (Motor OL Current)
% of P133 (Motor OL Current)
% of P133 (Motor OL Current)