0x2de0 | 0x35e0 - advanced settings, 0x2de0, 0x35e0 – Lenze i700 User Manual
Page 73: Loading the standard inverter characteristic, 5motor control & motor settings
Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05
73
5
Motor control & motor settings
5.7
Compensating for inverter influence on output voltage
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Advanced settings
For characteristic detection, the current controller is parameterised automatically at the beginning
of the identification process. For motors with a very low stator leakage inductance (< 1 mH), an
automatic parameter setting may fail and the actual identification process is aborted with an error
message like e.g. "short circuit".
• For such a case, it is possible to set the current controller manually via the object
(or
for axis B).
• Whether the current controller is to be selected automatically or the values below
(or
for axis B) are active, is selected via the object
for axis B).
0x2DE0 | 0x35E0 - Advanced settings
Loading the standard inverter characteristic
If an incorrect inverter characteristic has been determined or none at all, it is possible to load a
device-typical standard inverter characteristic.
How to load the standard inverter characteristic:
1. Set object
(or
• The progress of the procedure is shown in object
for axis B).
2. For permanent storage: After completion of the procedure, upload the inverter
(or
for axis B) to the controller from the i700 servo
inverter.
The »EASY Starter« serves to save the parameter settings of the i700 servo inverter as
parameter file (*.gdc). In the »PLC Designer«, this file can then be imported in the
corresponding axis.
Saving changed parameters safe against mains failure
Sub.
Name
Lenze setting
Data type
Current controller: Setting for identification
0: Automatic setting
UNSIGNED_8
Sensorless SM: Injection signal during test
mode
0: Off
UNSIGNED_8
Subindex 1:
Current controller: Setting for identification
Selection list
(Lenze setting printed in bold)
0 Automatic setting
1 Manual setting (0x2942/0x3142)
Write access CINH OSC P RX TX
UNSIGNED_8
Subindex 2:
Sensorless SM: Injection signal during test mode
Selection list
(Lenze setting printed in bold)
0 Off
1 On
Write access CINH OSC P RX TX
UNSIGNED_8