4.5
Monitoring of the DC-bus voltage
48
Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.5
Monitoring of the DC-bus voltage
For the device as a whole, the DC-bus voltage is monitored with regard to undervoltage and
overvoltage.
• The voltage monitoring is active in the device statuses "
"
" and "
• The warning thresholds for the monitoring are adjustable and preset for a rated mains voltage
of 400 V in the Lenze setting.
• The error thresholds for the monitoring result from the set rated mains voltage:
0x2540 - Device: Voltage values
Mains
Undervoltage thresholds
Overvoltage thresholds
Rated
voltage
Warning threshold
Error threshold
Threshold "Reset
error"
Warning threshold
Error threshold
Threshold "Reset
error"
60 V
430 V
10 V
15 V
795 V
60 V
50 V
230 V
eff
200 V
225 V
800 V
790 V
400 V
eff
285 V
430 V
800 V
790 V
480 V
eff
490 V
535 V
800 V
790 V
Greyed out = read access only or threshold specified
Sub.
Name
Lenze setting
Data type
Mains: Rated voltage
1: 400 Veff
UNSIGNED_8
Undervoltage (LU): Warning threshold
430 V
UNSIGNED_16
Undervoltage (LU): Error threshold
285 V
UNSIGNED_16
Undervoltage (LU): Threshold 'Reset error'
430 V
UNSIGNED_16
Overvoltage (OU): Warning threshold
795 V
UNSIGNED_16
Overvoltage (OU): Error threshold
800 V
UNSIGNED_16
Overvoltage (OU): Threshold 'Reset error'
790 V
UNSIGNED_16
Subindex 1:
Mains: Rated voltage
Selection of the mains voltage used with which the i700 servo inverter is operated.
Selection list
(Lenze setting printed in bold)
0 230 Veff
1 400 Veff
2 480 Veff
3 Reserved
4 60 V (setting-up operation)
Write access CINH OSC P RX TX
UNSIGNED_8
Subindex 2:
Undervoltage (LU): Warning threshold
Warning threshold for monitoring with regard to undervoltage
• If the DC-bus voltage of the i700 servo inverter falls below the threshold value set here, the device reports a
warning. Reset is effected with a hysteresis of 10 V.
Setting range
(min. value | unit | max. value)
Lenze setting
0
V
800 430 V
Write access CINH OSC P RX TX
UNSIGNED_16