Error code 0xff10: time-out, Error code 0xff11: numerical problem, Error code 0xff12: inverter error too big – Lenze i700 User Manual
Page 277: 9diagnostics & error management

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05
277
9
Diagnostics & error management
9.4
CiA402 error codes / error messages
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Error code 0xFF0D: No resolver connected --> command cannot be executed.
Text ID: 0x31
Error code 0xFF0E: Speed too low --> command cannot be executed.
Text ID: 0x32
Error code 0xFF0F: No resolver connected --> command cannot be executed.
Text ID: 0x33
Error code 0xFF10: Time-out
Text ID: 0x34
Error code 0xFF11: Numerical problem
Text ID: 0x35
Error code 0xFF12: Inverter error too big
Text ID: 0x36
Cause
Remedies
Response
The identification of a resolver error
was attempted during V/f
characteristic control without
feedback system.
The resolver error can only be
identified if the resolver is used as
feedback system during servo
control.
Warning
Cause
Remedies
Response
The actual speed is too low for the
resolver error to be identified.
Repeat identification at higher
speed.
Warning
Cause
Remedies
Response
The identification of a resolver error
was attempted but an encoder is
used as feedback system.
Identification is only possible with
devices with resolver feedback.
Warning
Cause
Remedies
Response
The actual speed is too low for the
resolver error to be identified.
Repeat identification at higher
speed.
Warning
Cause
Remedies
Response
The actual speed is too low for the
resolver error to be identified.
Repeat identification at higher
speed.
Warning
Cause
Remedies
Response
The results of the inverter error
identification are not plausible.
Check shielding of the motor cable.
Connect the shield with a surface as
large as possible.
Warning