61
5
Motor control & motor settings
5.3
Wiring check by means of manual test modes
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.3
Wiring check by means of manual test modes
Before the parameterisation of the actual control is started, the wiring of the motor (power and
encoder connection) should be checked for errors and, if required, should be corrected.
• For this purpose, the following manual test modes can be activated via object
for axis B) when the controller is inhibited:
•
Manual test mode "voltage/frequency"
•
Manual test mode "current/frequency"
• The parameters for the test modes can be adapted via object
for axis B). For
this, observe the notes in the description of the respective test mode.
0x2835 | 0x3035 - Manual test mode: Settings
Sub.
Name
Lenze setting
Data type
Manual test mode: Current setpoint
0 %
INTEGER_16
Manual test mode: Frequency
0.0 Hz
INTEGER_16
Manual test mode: Starting angle
0.0 °
INTEGER_16
Subindex 1:
Manual test mode: Setpoint current
Selection of the r.m.s. value of a phase current for test mode
• 100 % ≡ rated motor current (
for axis B)
Setting range
(min. value | unit | max. value)
Lenze setting
0
%
1000 0 %
Write access CINH OSC P RX TX
INTEGER_16
Subindex 2:
Manual test mode: Frequency
Selection of the frequency for test mode
Setting range
(min. value | unit | max. value)
Lenze setting
-1000.0
Hz
1000.0 0.0 Hz
Write access CINH OSC P RX TX
Scaling: 1/10
INTEGER_16
Subindex 3:
Manual test mode: Starting angle
Selection of the starting angle for test mode
Note!
In the case of the synchronous motor, a jerky compensating movement occurs after controller enable if the pole
position of this movement does not correspond to the starting angle.
Setting range
(min. value | unit | max. value)
Lenze setting
-1000.0
°
1000.0 0.0 °
Write access CINH OSC P RX TX
Scaling: 1/10
INTEGER_16