beautypg.com

7 setting the oscillation damping, Setting the oscillation damping, 5motor control & motor settings – Lenze i700 User Manual

Page 146

background image

5

Motor control & motor settings

5.14

Parameterising the V/f characteristic control

146

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.14.7

Setting the oscillation damping

The oscillation damping serves to reduce the oscillations during no-load operation which are caused

by energy oscillating between the mechanical system (mass inertia) and the electrical system (DC

bus). Furthermore, the oscillation damping can also be used to compensate resonances.

Function
The determination of the oscillation is based on the active current. In order to obtain the alternating

component of the active current, this current is differentiated. This signal is then passed through a

PT1 filter.

Identification of the oscillation
Before the oscillation damping can be parameterised, the oscillation has to be identified. One way

to do this is to examine the motor current while oscillation damping is switched off (gain = 0 %). At

steady-state operation, a constant current flows. If the drive oscillates, these oscillations are also

visible on the motor current. It is therefore possible to determine the frequency and the amplitude

of the oscillation from the alternating component of the motor current. In the following, this

alternating component is referred to as "current oscillation".

Note!

Observe the following restrictions:

• Damping is possible only for constant oscillations at a steady-state operating point.
• Oscillations occurring sporadically cannot be damped.
• Oscillation damping is not suitable for oscillations occurring during dynamic

processes (e.g. accelerations or load changes).

• Oscillation damping is only active if the setpoint speed is greater than 10 rpm and the

DC-bus voltage exceeds a value of 100 V.

0x2DD1:2 | 0x35D1:2

0x2B0A:2 | 0x330A:2

0x2B0A:1 | 0x330A:1

0x2B0A:4 | 0x330A:4

0x2B0A:3 | 0x330A:3

Q-current (iq): Actual current

Filter time

Gain

Ramp-end frequency

Limitation

Set value

mot. frequency

Oscillation damping