0x2ba5 | 0x33a5 - flying restart: delay time, 0x2ba6 | 0x33a6 - flying restart: result, 0x2ba5 – Lenze i700 User Manual
Page 152: 0x33a5, 0x2ba6, 0x33a6, 5motor control & motor settings
![background image](/manuals/566307/152/background.png)
5
Motor control & motor settings
5.14
Parameterising the V/f characteristic control
152
Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
0x2BA5 | 0x33A5 - Flying restart: Delay time
0x2BA6 | 0x33A6 - Flying restart: Result
To avoid starting a flying restart process at short-time controller inhibit, a time can be set here for the minimum
active controller inhibit time before a flying restart process is activated.
• Since a pulse inhibit > 500 ms causes a controller inhibit, this also applies to the pulse inhibit.
Setting range
(min. value | unit | max. value)
Lenze setting
0
ms
10000 0 ms
Write access CINH OSC P RX TX
UNSIGNED_16
Output of the speed found for acceptance in the control.
• This information is pending until the control reports acceptance of the found speed to the i700 servo inverter via
bit 0 in the Lenze control word (
or
for axis B).
Sub.
Name
Lenze setting
Data type
Flying restart: Determined speed [rpm]
INTEGER_16
Flying restart: Determined speed [n unit]
INTEGER_32
Subindex 1:
Flying restart: Determined speed [rpm]
Display area
(min. value | unit | max. value)
Initialisation
-32768
r/min
32767
Write access CINH OSC P RX TX
INTEGER_16
Subindex 2:
Flying restart: Determined speed [n unit]
Display area
(min. value | unit | max. value)
Initialisation
-480000
[n unit]
480000
Write access CINH OSC P RX TX
Scaling: 480000/2
31
INTEGER_32