The motor phase failure monitoring can be activated for both synchronous and asynchronous
motors. However, it is possible that a current flow cannot be detected for sure in the case of certain
operating states of synchronous motors that are connected correctly. Hence, a fault is triggered. The
following table provides an overview:
Special case: Hoist
The motor phase failure monitoring may trigger a fault message in a hoist if the asynchronous
motor applied for this purpose reaches the following working point:
• The hoist moves downwards, i.e. the motor is in generator mode.
• The slip frequency equals the field frequency in terms of amount. Both frequencies mutually
neutralise themselves due to their opposite effective directions.
Subindex 4:
Motor phase failure 2: Response
Monitoring 2 (in the "operation enabled" status):
Response during activation
Selection list
(Lenze setting printed in bold)
0 No response
1 Fault
2 Warning
Write access CINH OSC P RX TX
UNSIGNED_8
Operating status
Synchronous motor
Async. motor
Check of the motor phases prior to operation
Check of the motor phases during operation
I
q
< current threshold value
at standstill
when motor is rotating
I
q
≥ current threshold value
at standstill
when motor is rotating
Field weakening
when motor is rotating
Phase failure is detected for sure
The monitoring function may be activated without a fault pending.
I
q
Torque-forming current component
Note!
Monitoring during operation serves especially for applications which are operated with
constant load and speed. In all other cases, transient processes or unfavourable
operating points can cause maloperation.