Motor control & motor settings
5.3
Wiring check by means of manual test modes
64
Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Preconditions for the execution
• The motor must be able to rotate freely.
• The controller is free of errors and is in the "
" device status.
Response of the motor during the execution
The motor rotates as a function of the set output frequency.
How to activate the manual test mode "current/frequency":
1. If the controller is enabled, inhibit the controller.
Enable/inhibit operation via control word
2. Set object
(or
for axis B) to "2" to change to the "Current/frequency" test
mode.
3. Enable the controller to start the test mode.
4. To stop the test mode:
• Inhibit controller.
• Set object
(or
for axis B) to "0" to change back to the CiA402 mode.
Stop!
In the case of the synchronous motor, a jerky compensating movement occurs after
controller enable if the pole position of this movement does not correspond to the
starting angle.