Holding brake configuration
l
130
EDBCSXP064 EN 8.0
6.8
Holding brake configuration
I
Tip!
If you use a motor without a holding brake, you can skip this chapter.
v [m/s]
Bits:
or
or
or
Ctrl1.ProfEnable
Ctrl1.JogCCW
Ctrl1.JogCW
Ctrl1.RelLimSwitch
X25 (Relay)
Bit:
Stat1.Imp
C4023
C4021
C4021
C4022
C4022
t [s]
t [s]
t [s]
t [s]
ECSXA410
Fig. 6−22
Signal representation of the brake logic
)
Note!
If the brake logic is activated (C4020 = 1), the controller remains inhibited
(control bit Ctrl1.Rsp = 1) until a start command is effected via the control bits
Ctrl1.ProfEnable, Ctrl1.JogCCW, Ctrl1.JogCWor Ctrl1.RelLimSwitch, even if the
controller is enabled via X6/SI1 and X6/SI2.
Even if the brake logic is switched off (C4020=0), the brake relay is triggered
directly via the controller inhibit or internal pulse inhibit. When the controller
is inhibited, the brake is to close.
In the GDC, the parameters or codes to be set can be found in the parameter menu under
Short setup
W Brake.
ECSXA440
Fig. 6−23
GDC view: Short setup of the holding brake