Wiring of the standard device, Danger – Lenze EVS9332xK User Manual
Page 78
Wiring of the standard device
Important notes
Protection of persons
5.1
5.1.1
l
5.1−2
EDSVS9332K EN 8.0−07/2013
The terminals X1 and X5 have double (reinforced) insulation according to
EN50178. The protection against accidental contact is ensured without
additional measured being taken.
{
Danger!
ƒ
The terminals X3, X4, X6, X7, X8, X9, X10, X11 have basic
insulation (single isolating distance).
ƒ
In the event of a defective isolating distance, protection
against accidental contact can only be guaranteed by taking
external measures such as double insulation.
ƒ
If an external DC 24 V voltage source is used, the insulation
degree of the controller depends on the insulation degree of
the voltage source.
59 39 A1 A2 A3 A4 E1 E2 E3 E4 E5
ST1 ST2
28
L1
24 VDC
N
X1
X5
X3 X4 X6 X7 X8 X9 X10 X11
W
V
U
PE
PE
L1
L2
L3
+U
G
-U
G
9300std084
Fig. 5.1−1
Electrical isolation between power terminals, control terminals and housing
Double (reinforced) insulation
Basic insulation
Only replace defective fuses in the deenergised state to the type specified.
Only carry out the safety−related disconnection of the controller from the
mains via a contactor on the input side or a manually operated toggle switch.
Electrical isolation
Replacing defective fuses
Disconnecting the controller