Wiring of the system bus (can), Wiring of the standard device, Stop – Lenze EVS9332xK User Manual
Page 153: 9 wiring of the system bus (can)
Wiring of the standard device
Wiring of the system bus (CAN)
5.9
l
5.9−1
EDSVS9332K EN 8.0−07/2013
5.9
Wiring of the system bus (CAN)
A
1
A
2
A
3
A
n
93XX
93XX
93XX
GND
GND
GND
GND
LO
LO
LO
LO
HI
HI
HI
HI
X4
X4
X4
PE
PE
PE
PE
120
120
9300VEC054
Fig. 5.9−1
System bus (CAN) wiring
A
1
Bus device 1 (controller)
A
2
Bus device 2 (controller)
A
3
Bus device 3 (controller)
A
n
Bus device n (e. g. PLC), n = max. 63
X4/GND
CAN−GND: System bus reference potential
X4/LO
CAN−LOW: System bus LOW (data line)
X4/HI
CAN−HIGH: System bus HIGH (data line)
(
Stop!
Connect a 120
W terminating resistor to the first and last bus
device.
We recommend the use of CAN cables in accordance with ISO 11898−2:
CAN cable in accordance with ISO 11898−2
Cable type
Paired with shielding
Impedance
120
W (95 ... 140 W)
Cable resistance/cross−section
Cable length
£ 300 m £ 70 mW/m / 0.25 0.34 mm
2
(AWG22)
Cable length 301 1000 m
£ 40 mW/m / 0.5 mm
2
(AWG20)
Signal propagation delay
£ 5 ns/m
Wiring