Configuration, Code table – Lenze EVS9332xK User Manual
Page 283
Configuration
Code table
8.4
l
8.4−9
EDSVS9332K EN 8.0−07/2013
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0126 MONIT CE0
3
0
2
3
TRIP
Warning
Off
Configuration of CE0
Configuration of communication error
monitoring with automation interface CE0
C0127 OC8 LIMIT
0
0
{1 %}
120 Threshold for I
2
× t advance warning (motor)
l
0 = I
2
× t advance warning switched off
l
I
2
× t > C0127
ð Fault message OC8
(response set in C606)
C0128 TAU MOTOR
5.0
0.1
{0.1 min}
50.0 Thermal time constant of the motor
The time constant is required for calculating
the I
2
× t disconnection.
C0130 ACT TI
g
NSET act. Ti times
Active T
i
times of NSET
C0134 RFG CHARAC
0
0
1
Linear
S−shaped
NSET RFG characteristic
Characteristic of ramp function generator for
main setpoint
C0135 CONTROL
WORD
0
0
{1}
65535 Control word
Controller control word for LECOM−A/B/LI or
keypad.
C0136
g
1 CTRLWORD
C135
Control word C135
2 CTRLWORD
CAN
Control word CAN
3 CTRLWORD AIF
Control word AIF
C0141 FCODE
(SETVAL)
0.0
−199.9
{0.1 %}
199.9 Main setpoint
C0142 START
OPTIONS
1
Start options
0
Start lock
l
Automatic start inhibited after
– mains connection
– cancelling of a message (t > 0.5 s)
– TRIP reset
l
Start after HIGH−LOW−HIGH level change
at X5/28
1
Auto start
Automatic start when X5/28 = HIGH
C0150 STATUS WORD
g 0
{1}
65535 Status word when networked with
automation interfaces
l
Binary interpretation indicates the bit
states
C0151 FDO (DW)
g
Display (hex.) of the free digital output
signals configured with C0116
l
Binary interpretation indicates the bit
states
C0155 STATUS WORD
2
g Bit00
Fail
Bit08
CW/CC
W
Status word 2
Extended decimal status word
l
Binary interpretation indicates the bit
states
Bit01
Mmax
Bit09
—
Bit02
Imax
Bit10
—
Bit03
IMP
Bit11
—
Bit04
RDY
Bit12
—
Bit05
CINH
Bit13
—
Bit06
Trip
Bit14
—
Bit07
Init
Bit15
—