Configuration, Code table – Lenze EVS9332xK User Manual
Page 300
Configuration
Code table
8.4
l
8.4−26
EDSVS9332K EN 8.0−07/2013
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0582 MONIT OH4
2
2
3
Warning
Off
OH4 monitoring
Configuration of heatsink temperature
monitoring
C0583 MONIT OH3
®
0
2
3
Trip
Warning
Off
OH3 monitoring
Configuration of monitoring for "fixed motor
temperature"
à
Depending on C0086
C0584 MONIT OH7
®
2
3
Warning
Off
OH7 monitoring
Configuration of monitoring for "adjustable
motor temperature"
à
Depending on C0086
Temperature monitoring via resolver input
C0585 MONIT OH8
3
0
2
3
Trip
Warning
Off
OH8 monitoring
Configuration of monitoring for "adjustable
motor temperature"
Temperature monitoring via PTC input
C0586 MONIT SD2
0
0
2
3
Trip
Warning
Off
SD2 monitoring
Configuration of resolver monitoring
C0587 MONIT SD3
3
0
2
3
Trip
Warning
Off
SD3 monitoring
Configuration of monitoring for "encoder at
X9"
C0588 MONIT
H10/H11
0
0
Trip
H10 / H11 monitoring
2
3
Warning
Off
Only Lenze service personnel is permitted to
set C0588 = 2 or C0588 = 3
C0589 MONIT P03
2
0
2
3
Trip
Warning
Off
P03 monitoring
Configuration of following error monitoring
l
Function block DFSET monitors the
following error. Monitoring is only active if
DFSET is used.
C0590 MONIT P13
0
0
2
3
Trip
Warning
Off
P13 monitoring
Configuration of phase error monitoring
l
Function block DFSET monitors the
following error. Monitoring is only active if
DFSET is used.
C0591 MONIT CE1
3
0
2
3
Trip
Warning
Off
CE1 monitoring
Configuration of "CAN−IN1 error" monitoring
C0592 MONIT CE2
3
0
2
3
Trip
Warning
Off
CE2 monitoring
Configuration of "CAN−IN2 error" monitoring
C0593 MONIT CE3
3
0
2
3
Trip
Warning
Off
CE3 monitoring
Configuration of "CAN−IN3 error" monitoring
C0594 MONIT SD6
®
0
2
3
Trip
Warning
Off
SD6 monitoring
Configuration of "motor temperature sensor"
monitoring
à
Depending on C0086
C0595 MONIT CE4
3
0
2
3
Trip
Warning
Off
CE4 monitoring
Configuration of "CAN bus off" monitoring
C0596 NMAX LIMIT
5500 0
{1 rpm}
16000 System speed monitoring
C0597 MONIT LP1
3
0
2
3
Trip
Warning
Off
LP1 monitoring
Configuration of motor phase failure
monitoring
C0598 MONIT SD5
3
0
2
3
Trip
Warning
Off
SD5 monitoring
Configuration of monitoring for master
current at X5/1.2 < 2 mA