Mains choke/mains filter assignment, Wiring of the standard device – Lenze EVS9332xK User Manual
Page 126
Wiring of the standard device
Standard devices with a power of 45 kW
Mains choke/mains filter assignment
5.6
5.6.5
l
5.6−6
EDSVS9332K EN 8.0−07/2013
Supply conditions
Range
Description
Fuses
l
Only according to UL 248
l
Mains short−circuit current up to 10000 A
rms
: All classes permissible
l
Mains short−circuit current up to 50000 A
rms
: Only classes "J", "T" or "R"
permissible
Cables
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following
conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Observe all national and regional regulations!
9300
Rated fuse current
Cable cross−section
Fuse
L1, L2, L3, PE
Type
[A]
[AWG]
Operation with mains choke/mains filter
EVS9330−xK
100
1
5.6.5
Mains choke/mains filter assignment
9300
Mains choke
Interference voltage category according to EN 61800−3 and motor cable length
Component
Component
Type
C2
max. [m]
C1
max. [m]
EVS9330−xK
ELN3−0038H085
EZN3A0030H110
25
EZN3B0030H110
50
EZN3A0030H110N001
3)
25
E82ZN55334B230
50
3)
For controllers with thermal separation
Installation to UL