Technical data, Rated data overcurrent operation, 2 operation at 480 v – Lenze EVS9332xK User Manual
Page 47
Technical data
Rated data
Overcurrent operation
3.3
3.3.3
l
3.3−5
EDSVS9332K EN 8.0−07/2013
9300
Output currents
8 kHz
1)
16 kHz
1)
Rated current
Continuous
thermal
current
3)
Maximum
current
2)
Standstill
current
Rated current
Continuous
thermal
current
3)
Maximum
current
2)
Standstill
current
Type
I
r8
[A]
I
r8
[A]
I
M8
[A]
I
08
[A]
I
r16
[A]
I
r16
[A]
I
M16
[A]
I
016
[A]
EVS9321−xK
1.5
1.05
3.0
3.0
1.1
0.77
2.2
2.2
EVS9322−xK
2.5
1.75
5.0
5.0
1.8
1.26
3.6
3.6
EVS9323−xK
3.9
2.73
7.8
7.8
2.9
2.03
5.8
5.8
EVS9324−xK
7.0
4.9
14.0
14.0
5.2
3.64
10.4
10.4
1)
Switching frequency of the inverter
2)
The currents apply to a periodic load change cycle with max. 10 seconds overcurrent duration and
50 seconds base load duration at max. 44 % of the rated current
3)
70 % of the rated current
3.3.3.2
Operation at 480 V
Basis of the data
Voltage
Frequency
Supply
3/PE 480 V AC
[U
r
]
320 V − 0 % ... 528 V + 0 %
45 Hz − 0 % ... 65 Hz + 0 %
DC 678 V (alternatively)
[U
DC
]
460 V − 0 % ... 740 V + 0 %
˘
Output voltage
With mains choke
3 ~ 0 ... approx. 94 % U
r
˘
Without mains choke
3 ~ 0 ... U
r
˘
9300
Mains current
1)
Typical motor power
Output power
Power loss
With
mains choke
Without
mains choke
ASM
(4−pole)
8 kHz
2)
U, V, W
+U
G
, −U
G
3)
Type
I
r
[A]
I
r
[A]
P
r
[kW]
P
r
[hp]
S
r8
[kVA]
P
DC
[kW]
P
V
[W]
EVS9321−xK
1.5
2.1
0.37
0.5
1.2
2.0
100
EVS9322−xK
2.5
3.5
0.75
1.0
2.1
0.75
110
EVS9323−xK
3.9
5.5
1.5
2.0
3.2
2.2
140
EVS9324−xK
7.0
˘
3.0
4.0
5.8
0.75
200
Bold print = Lenze setting
1)
Mains currents at 8 kHz switching frequency
2)
Switching frequency of the inverter
3)
Power which can additionally be drawn from the DC bus at operation with power−adapted motor
9300
Output currents
8 kHz
1)
16 kHz
1)
Rated current
Continuous
thermal
current
3)
Maximum
current
2)
Standstill
current
Rated current
Continuous
thermal
current
3)
Maximum
current
2)
Standstill
current
Type
I
r8
[A]
I
r8
[A]
I
M8
[A]
I
08
[A]
I
r16
[A]
I
r16
[A]
I
M16
[A]
I
016
[A]
EVS9321−xK
1.5
1.05
3.0
3.0
1.1
0.77
2.2
2.2
EVS9322−xK
2.5
1.75
5.0
5.0
1.8
1.26
3.6
3.6
EVS9323−xK
3.9
2.73
7.8
7.8
2.9
2.03
5.8
5.8
EVS9324−xK
7.0
4.9
14.0
14.0
5.2
3.64
10.4
10.4
1)
Switching frequency of the inverter
2)
The currents apply to a periodic load change cycle with max. 10 seconds overcurrent duration and
50 seconds base load duration at max. 44 % of the rated current
3)
70 % of the rated current