Mounting in "cold plate" technique, Installing of the standard device – Lenze EVS9332xK User Manual
Page 56
Installing of the standard device
Standard devices in the power range 0.37 ... 11 kW
Mounting in "cold plate" technique
4.1
4.1.4
l
4.1−4
EDSVS9332K EN 8.0−07/2013
4.1.4
Mounting in "cold plate" technique
The drive controllers can be mounted in ˜cold plate˜ technique, e.g. on
collective coolers. For this purpose, the drive controllers of type EVS93xx−CKx
must be used.
Mounting material required from the scope of supply:
Description
Use
Quantity
EVS9321−CK
EVS9322−CK
EVS9323−CK
EVS9324−CK
EVS9325−CK
EVS9326−CK
Fixing bracket
Controller fixing
2
2
2
Sheet metal screw
3.5 × 13 mm (DIN 7981)
Mounting the fixing
bracket to the controller
6
6
6
The following points are important for safe and reliable operation of the
controller:
ƒ Good thermal connection to the cooler
– The contact surface between the collective cooler and the controller
must be at least as large as the cooling plate of the controller.
– Plane contact surface, max. deviation 0.05 mm.
– When attaching the collective cooler to the controller, make sure to
use all specified screw connections.
ƒ Observe the thermal resistance R
th
given in the table. The values are
valid for controller operation under rated conditions.
9300
Cooling path
Power to be dissipated
Heatsink − environment
Type
P
v
[W]
R
th
[K/W]
EVS9321−CK
24
1.45
EVS9322−CK
42
0.85
EVS9323−CK
61
0.57
EVS9324−CK
105
0.33
EVS9325−CK
180
0.19
EVS9326−CK
360
0.10
ƒ The rated data and the derating factors at increased temperature also
apply to the ambient temperature of the drive controllers.
ƒ Temperature at the cooling plate of the drive controller: max. 75 °C.
Requirements for collective
coolers
Ambient conditions