Troubleshooting and fault elimination, System error messages general error messages – Lenze EVS9332xK User Manual
Page 405
Troubleshooting and fault elimination
System error messages
General error messages
9.3
9.3.1
l
9.3−5
EDSVS9332K EN 8.0−07/2013
Remedy
Cause
Description
Fault message
Remedy
Cause
Description
Display
No.
x089
PL
Error during rotor position
adjustment (the error is saved
with mains failure protection)
l
The rotor position adjustment
was cancelled.
l
During rotor position
adjustment with an absolute
value encoder the error Sd7 or
SD8 occurred.
Repeat rotor position adjustment.
^ 6.8−1
Note: After an Sd7 fault it is
absolutely required to carry out
another rotor position
adjustment. Otherwise the drive
may carry out uncontrolled
movements after controller
enable. The drive must not be
commissioned without a
successfully executed rotor
position adjustment!
x091
EEr
External monitoring has been
triggered via DCTRL.
A digital signal assigned to the
TRIP−SET function has been
activated.
l
Check external encoder.
l
Switch off the monitoring
(C0581 = 3).
0105
H05
Internal fault (memory)
Contact Lenze.
0107
H07
Internal fault (power stage)
During initialisation of the
controller, an incorrect power
stage was detected.
Contact Lenze.
x110
H10
Heatsink temperature sensor
error
Sensor for detecting the heatsink
temperature indicates undefined
values.
l
Contact Lenze.
l
Switch off the monitoring
(C0588 = 3).
x111
H11
Temperature sensor error:
Temperature inside the controller
Sensor for detecting the internal
temperature indicates undefined
values.
l
Contact Lenze.
l
Switch off the monitoring
(C0588 = 3).
x153
P03
Following error
The angle difference between set
and actual position is larger than
the following error limit set under
C0255.
l
Increase following error limit
under C0255.
l
Switch off the monitoring
(C0589 = 3).
Drive cannot follow the digital
frequency (I
max
limit).
Check drive dimensioning.
x163
P13
Angle overrun.
l
Phase controller limit reached
l
Drive cannot follow the digital
frequency (I
max
limit).
l
Enable drive
l
Check drive dimensioning.
x166
P16
Faulty transfer of system bus
(CAN) sync telegram.
The sync telegram from the
master (PLC) is out of sync cycle.
l
Set the "sync cycle" to the
transmission cycle of the
master (PLC) under C1121.
l
Note:
– C0362 displays the time
interval between 2 sync
telegrams.
– C0362 = 0: communication
interrupted.
The sync telegram of the master
(PLC) is not received.
l
Check communication channel.
l
Check baud rate, controller
address.
l
Note:
– C0362 displays the time
interval between 2 sync
telegrams.
– C0362 = 0: communication
interrupted.
The controller is enabled too fast.
Delay the controller enable.
The time delay required depends
on the time interval between the
sync telegrams.