Switch-on sequence, Switch−on sequence, Commissioning – Lenze EVS9332xK User Manual
Page 169: Stop
Commissioning
Switch−on sequence
6.3
l
6.3−1
EDSVS9332K EN 8.0−07/2013
6.3
Switch−on sequence
(
Stop!
When commissioning is completed, do not enable the controller
before
ƒ
CDATA−INIT−NOUT
= LOW when using function block CDATA.
ƒ
CURVEC1−INIT−DFOUT = LOW when using function block
CURVEC1.
Switch−on sequence
Note
1.
Ensure that the controller inhibit is active after
mains connection
misc008
59
28
X5
}
Terminal X5/28 = LOW
2.
Ensure that there is no external error
Terminal X5/E4 = HIGH
3.
Switch on controller
A
The control card is operated via an external voltage
supply:
Switch on the external DC 24 V supply voltage
ON
misc002
B
The control card is operated via the internal voltage
supply:
Switch on the mains. The controller provides the
DC 24 V supply.
4.
The controller is initialised after approx. 2 s
5.
Switch on the PC and start GDC
GDC starts in the online mode if the PC
is connected to the controller.
Information on how to establish a
connection is given in the "Global Drive
Control (GDC) − Getting started"
manual.
6.
Set the machine parameters in GDC
A
Select the basic configuration
Lenze setting: C0005 = 10000 (basic configuration
˜Cam profiler˜)
^ 6.5−2
B
Adapt controller to the mains
^ 6.5−2
C
Enter gearbox and feed constants
^ 6.5−3
D
Enter motor data
^ 6.5−5
E
Set the temperature monitoring of the motor
Motor with PTC or thermal contact:
^ 6.5−17
Motor with KTY:
^ 6.5−18
F
Select the feedback system
^ 6.6−1
7.
Carry out a current controller adjustment if
necessary
^ 6.7−1
8.
Carry out a rotor position adjustment if necessary
^ 6.8−1
9.
Configure the control terminal functions in order to
adapt them to your application.
For internal voltage supply, assign X5/x
with "FIXED1"and X6/x with
"FIXED100%".
^ 6.9−1
10.
Create the motion profile
^ 6.10−1
11.
Save the motion profile
^ 6.10−6
12.
Transfer the motion profile to the controller
^ 6.11−1
13.
Save the settings safe from power failure in one of
the 4 parameter sets (C0003)
With C0003 = 1 the settings are stored in parameter
set 1.
After connecting the DC 24 V supply or
after mains connection, parameter set
1 is activated automatically.
(See chapter "Parameter setting")