Configuration – Lenze EVS9332xK User Manual
Page 289
Configuration
Code table
8.4
l
8.4−15
EDSVS9332K EN 8.0−07/2013
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0329 ADAPT ON/OFF
0
PCTRL1 Adaptation On/Off
Activation of process controller adaptation
0
no process controller adaptation
(C0222)
1
PCTRL1−ADAPT + linear characteristic
2
PCTRL1−ADAPT + 3−point characteristic
3
System deviation + 3−point
characteristic
C0332 PCTRL1 TIR
0.000 0.000
{0.001 s}
999.900 PCTRL1
Acceleration time Tir
(referring to setpoint change 0 ... 100 %)
C0333 PCTRL1 TIF
0.000 0.000
{0.001 s}
999.900 PCTRL1
Deceleration time Tif
(referring to setpoint change 0 ... 100 %)
C0336 ACT VP
g 0.0
{0.1}
500.0 PCTRL1
Actual V
p
C0337 BI/UNIPOLAR
0
0
1
Bipolar
Unipolar
PCTRL1
Bipolar/unipolar range of action
C0338 ARIT1 FUNCT
1
0
1
2
3
4
5
15
OUT = IN1
OUT = IN1 + IN2
OUT = IN1 − IN2
OUT = IN1 × IN2
OUT = IN1 / IN2
OUT = IN1 / (100% – IN2)
OUT = IN1 % IN2
ARIT1
Function selection
C0339
s
® Selection list 1 ARIT1
Configuration of analog input signals
1 ARIT1−IN1
1000 FIXED0%
2 ARIT1−IN2
1000 FIXED0%
C0340
g
ARIT1
Display of analog input signals
1 (C0339/1)
2 (C0339/2)
C0350 CAN ADDRESS
1
1
{1}
63 CAN
System bus node address
l
Change becomes effective after ˜reset
node˜ command
C0351 CAN
BAUDRATE
0
0
1
2
3
4
500 kbps
250 kbps
125 kbps
50 kbps
1000 kbps
CAN
System bus baud rate
l
Change becomes effective after ˜reset
node˜ command
C0352 CAN MST
0
0
1
Slave
Master
CAN
Configuration of system bus node
l
Change becomes effective after ˜reset
node˜ command
C0353
0
1
C0350
C0354
CAN
Source for system bus address
1 CAN ADDR
SEL1
0
CAN−IN1, CAN−OUT1
2 CAN ADDR
SEL2
0
CAN−IN2, CAN−OUT2
3 CAN ADDR
SEL3
0
CAN−IN3, CAN−OUT3