Wiring of the standard device – Lenze EVS9332xK User Manual
Page 129
Wiring of the standard device
Standard devices with a power of 45 kW
Motor connection
5.6
5.6.6
l
5.6−9
EDSVS9332K EN 8.0−07/2013
)
Note!
ƒ
We recommend to use Lenze system cables for wiring.
ƒ
For self−made cables only use cables with shielded cores
twisted in pairs.
PE U
V
W
T1 T2
-UG +UG
PES
PES
PE
M
3~
PES
PES
KTY
X8/5
X7/9
X8/8
X7/8
PES
X8
X7
X9
X10
9300std073
Fig. 5.6−5
Circuit diagram for the motor connection with KTY temperature sensor at X7 or X8
Features of the connection for motor temperature monitoring:
Pins X7/8, X7/9 of resolver input (X7), or
pins X8/8, X8/5 of incremental encoder input (X8)
Connection
Linear KTY temperature sensor
Tripping point
l
Warning: adjustable
l
Error (TRIP): fixed at 150 °C
Notes
l
Monitoring is not active in the Lenze setting.
l
The KTY temperature sensor is monitored with regard to
interruption and short circuit.
Motor with KTY thermal
sensor