DC−bus operation
Conditions for trouble−free DC−bus operation
10.2
l
10.2−1
EDSVS9332K EN 8.0−07/2013
10.2
Conditions for trouble−free DC−bus operation
ƒ Distributed supply (parallel mains supply):
– Always use the prescribed mains choke when connecting a controller
to the mains.
– Controllers of the EVx9321 ... EVx9333, 8200 and 8200 vector series
must not be connected to the mains if they are operated in a DC−bus
connection with EVx9335 ... EVx9338 and EVx9381 ... EVx9383
controllers.
ƒ Only controllers with identical mains voltage/DC bus voltage ranges
can be operated in a DC−bus connection:
– Set the mains voltage/DC−bus voltage under C0173.
ƒ 9340 regenerative power supply modules and 9360 DC input modules
cannot be used together in the DC−bus connection.
ƒ Read the documentation for the other controllers connected to the DC
bus with regard to "DC−bus operation".