Overcurrent operation, Technical data – Lenze EVS9332xK User Manual
Page 46
Technical data
Rated data
Overcurrent operation
3.3
3.3.3
l
3.3−4
EDSVS9332K EN 8.0−07/2013
3.3.3
Overcurrent operation
Under the operating conditions described here, the
EVS9321−xK ... EVS9324−xK controllers can supply a rated output current
which is up to twice as high.
)
Note!
If you enter values > 1.5 × rated output current under C0022, the
controller switches to overcurrent operation.
ƒ
Switching between overcurrent operation and standard
operation is only possible if the controller is inhibited
(X5/28 = LOW).
ƒ
The continuous current is automatically reduced to 70 % of
the rated output current.
3.3.3.1
Operation at 400 V
Basis of the data
Voltage
Frequency
AC mains connection
[V
rate
d
]
3/PE AC 320 V − 0 % ... 440 V + 0 %
45 Hz − 0 % ... 65 Hz + 0 %
DC−mains connection
(alternatively)
[U
DC
]
DC 450 V − 0 % ... 620 V + 0 %
˘
Output voltage
With mains choke
3 ~ 0 approx. 94 % V
rated
˘
Without mains choke
3 ~ 0 ... U
N
˘
9300
Mains current
1)
Typical motor power
Output power
Power loss
With
mains choke
Without
mains choke
ASM
(4−pole)
8 kHz
2)
U, V, W
+U
G
, −U
G
3)
Type
I
r
[A]
I
r
[A]
P
r
[kW]
P
r
[hp]
S
r8
[kVA]
P
DC
[kW]
P
V
[W]
EVS9321−xK
1.5
2.1
0.37
0.5
1.0
2.0
100
EVS9322−xK
2.5
3.5
0.75
1.0
1.7
0.75
110
EVS9323−xK
3.9
5.5
1.5
2.0
2.7
2.2
140
EVS9324−xK
7.0
˘
3.0
4.0
4.8
0.75
200
Bold print = Lenze setting
1)
Mains currents at 8 kHz switching frequency
2)
Switching frequency of the inverter
3)
Power which can additionally be drawn from the DC bus at operation with power−adapted motor