Troubleshooting and fault elimination, System error messages general error messages – Lenze EVS9332xK User Manual
Page 403
Troubleshooting and fault elimination
System error messages
General error messages
9.3
9.3.1
l
9.3−3
EDSVS9332K EN 8.0−07/2013
Remedy
Cause
Description
Fault message
Remedy
Cause
Description
Display
No.
x065
CE4
BUS−OFF state of system bus
(CAN)
The controller has received too
many faulty telegrams via the
system bus (CAN) and has
disconnected from the bus.
l
Check wiring at X4: Is the bus
correctly terminated?
l
Check shield connection of the
cables.
l
Check PE connection.
l
Check bus load, reduce the
baud rate if necessary.
(Observe the cable length!)
l
Switch off the monitoring
(C0595 = 3).
0071
CCr
System failure
Strong interference injection on
the control cables
Screen control cables
Ground or earth loops in the
wiring
l
Check wiring
l
Check PE connection
After troubleshooting: Deenergise
the device completely (disconnect
24 V supply, discharge DC bus)!
0072
PR1
Checksum error in parameter
set 1
CAUTION: The Lenze setting is
loaded automatically!
l
Fault when loading a
parameter set.
l
Interruption while
transmitting the parameter set
via keypad.
l
Set the required parameters
and store them under C0003 =
1.
l
As to PLC devices, check the
use of pointers.
The stored parameters are
incompatible with the loaded
software version.
Store the parameter set under
C0003 = 1 first to allow for a
faults reset.
0074
PEr
Program error
Error in the program flow
Send the parameter set (on floppy
disk/CD−ROM) with a detailed
description of the problem to
Lenze.
After troubleshooting: Deenergise
the device completely (disconnect
24 V supply, discharge DC bus)!
0075
PR0
Error in parameter set.
The operating system software
has been updated.
Storage of the Lenze setting
C0003 = 1.
After troubleshooting: Deenergise
the device completely (disconnect
24 V supply, discharge DC bus)!
0079
PI
Fault during parameter
initialisation
l
An error has been detected
during the parameter set
transfer between two devices.
l
The parameter set does not
match the controller, e.g. if
data has been transferred from
a higher−power controller to a
lower−power controller.
l
Correct parameter set.
l
Send parameter set (on floppy
disk/CD−ROM) and a detailed
description of the problem to
Lenze.
x082
Sd2
Resolver error at X7
Resolver cable interrupted.
l
Check cable for open circuit.
l
Check resolver.
l
Switch off the monitoring
(C0586 = 3).
x083
Sd3
Encoder error at X9
Cable interrupted.
Check cable for open circuit.
Pin X9/8 not connected.
Apply 5 V to pin X9/8 or switch off
monitoring (C0587 = 3).
x085
Sd5
Encoder error at X6/1 and X6/2
(C0034 = 1)
Current signal at X6/1 X6/2 <
2mA.
l
Check cable for open circuit.
l
Check current signal encoder.
l
Switch off monitoring
(C0598 = 3).
x086
Sd6
Motor temperature sensor error
(X7 or X8)
Encoder for detecting the motor
temperature at X7 or X8 indicates
undefined values.
l
Check cable for firm
connection.
l
Switch off the monitoring
(C0594 = 3).