Troubleshooting and fault elimination – Lenze EVS9332xK User Manual
Page 410
Troubleshooting and fault elimination
Error messages during profile download
9.4
l
9.4−4
EDSVS9332K EN 8.0−07/2013
Remedy
Cause
Fault name
Code
C0505/4
Pointer on Y values, selection of an interpolation point on the Y axis
INV_LENGTH_RANGE The selected interpolation
point does not exist.
Observe the existing number of interpolation points under
C0391/x.
C0511/1
Write X values in physical units [m_units] with automatic indexing of the address pointer (auto−increment)
INV_LENGTH_RANGE Attempt to write beyond the
data field.
l
Limit the number of writing cycles to the existing number of
interpolation points (see C0391/x).
l
Set the pointer to the beginning of the value table
(C0505/3 = 0).
INV_COLLISION_
RANGE
Relative data model is used
(Lenze setting). The address
pointer has not been
incremented.
Use GDC to create a profile with the absolute data model, load
it into the controller and accept it.
INV_VALUE_RANGE
Attempt to transfer a
non−zero value as the first X
value
Enter 0" for the first X value.
C0511/2
Read X values in physical units [m_units] with automatic indexing of the address pointer (auto−increment)
INV_LENGTH_RANGE Attempt to read beyond the
data field.
l
Limit the number of reading cycles to the existing number of
interpolation points (see C0391/x)
l
Set the pointer to the beginning of the value table
(C0505/5 = 0).
C0512/1
Write Y values in physical units [s_units] with automatic indexing of the address pointer (auto−increment)
INV_LENGTH_RANGE Attempt to write beyond the
data field.
l
Limit the number of writing cycles to the existing number of
interpolation points (see C0391/x).
l
Set the pointer to the beginning of the value table
(C0505/4 = 0).
INV_VALUE_RANGE
The relative data model is
selected.
While writing the Y value,
the representable value
range has been exceeded .
l
Observe the maximum permissible difference between Y
values of
32767 inc.
l
This profile requires a larger number of interpolation points.
l
Increase the number of interpolation points (via GDC) and
completely repeat the transfer of the profile.
C0512/2
Read Y values in physical units [m_units] with automatic indexing of the address pointer (auto−increment)
INV_LENGTH_RANGE Attempt to read beyond the
data field.
l
Limit the number of reading cycles to the existing number of
interpolation points (see C0391/x).
l
Set the pointer to the beginning of the value table
(C0505/6 = 0).